MOQ (Minimum Bestellquantitéit): méi wéi 10 Sets
ATS Schalter SKT Serie Haapttechnesch Parameteren | |||||||||||||
SKX2 | SKT1 | ||||||||||||
Frame-Bewäertungsstroum (Inm) | 100A | 160A | 250A | 630A | 1600A | 3200A | |||||||
Bewäertungsstroum (Inn) | 100 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | 1600 | 2000 | 2500 | 3200 |
Bewäert onënnerbrach Stroum (Ith) | 10,16,20,25,32,40,50,63,80, 100A | 63,80,100,125, 140,150,160A | 160,180,200,225,250A | 160,180,200,225, 250,315,350,400, 500,630A | 800, 1000, 1250, 1600A | 2000, 2500, 3200A | |||||||
Bewäert Isolatiounsspannung (Ui) | 660V | 800V | |||||||||||
Bewäert Impulsspannung (Uimp) | 6KV | 8KV | |||||||||||
Bewäert Betribsspannung (Ue) | AC440V | ||||||||||||
Notzungskategorie | AC-33A | ||||||||||||
Bewäertungsstroum (dh) | 10,16,20,25,32,40,50,63,80,100,125,160,180,200,225,250,315,350,400,500,630A | 800, 1000, 1250, 1600, 2000, 2500, 3200A | |||||||||||
Bewäert Kuerzschlusskapazitéit (Icm) | 10 L | ||||||||||||
Bewäert Break Circuit Kapazitéit (Ics) | 10 L | ||||||||||||
Bewäert Limit Kuerzschlussstroum (Icu) | 7KA | 13KA | 35KA | 50KA | 75KA | ||||||||
Schaltzäit | 1,2S | 0,6S | 1,2S | 2.4S | |||||||||
Kontrollspannung | AC220V (DC24V, DC110V, DC220V, AC110V, AC280V) | ||||||||||||
Elektreschen Energieverbrauch | 40W | 325W | 355W | 400W | 440W | 600W | |||||||
18W | 62W | 74W | 90W | 98W | 120W | ||||||||
Gewiicht | 3.5 | 5.3 | 5.5 | 7 | 17 | 17,5 | 37 | 44 | 98 |